Roundtrip efficiency

Roundtrip efficiency is a key performance metric for an energy storage system (ESS) that characterizes the energy lost during a full charge–discharge cycle. It is defined as the ratio of the energy output from the system during discharge to the energy input supplied during charging. A higher round-trip efficiency indicates lower energy losses and operational costs.

The efficiency can be expressed as a percentage using the formula:

Round-trip efficiency greatly affects the economics of energy storage systems, particularly for applications in grid stability, renewable energy integration, and peak demand management.

Factors affecting efficiency

The round-trip efficiency of a storage system accounts for losses from multiple sources. These can include:

For the green hydrogen and green ammonia the main factors are:

Comparison of storage methods

Different energy storage technologies exhibit a wide range of round-trip efficiencies. The technology is often selected based on its intended application, such as providing power quality and distributed power or serving as bulk energy storage.

Comparison of Round-trip Efficiency for Energy Storage Methods
Storage Technology Median Efficiency (%) Efficiency Range (%)
Lead-acid battery ~75% ~60% – 90%
Li-ion battery ~90% ~85% – 95%
Sodium–sulfur battery   ~60% – 90%
Flywheel ~92% ~85% – 95%
Supercapacitor   85% – 95%
Superconductive ~90% ~85% – 97%
Compressed air ~52% ~41% – 90%
Thermal ~40% ~30% – 50%
Pumped hydro ~75% ~65% – 85%
Redox flow   60% – 75%
Green hydrogen ~40% 28 – 52%
Green ammonia   23 – 42%

See also

References

  1. 1 2 3 4 Penthia 2025, p. 290.
  2. 1 2 Kojima 2025, p. 2.
  3. ↑ Ma, Glatzmaier & Kutscher 2011.
  4. ↑ Ma, Glatzmaier & Kutscher 2011, p. 9, Figure 9.
  5. ↑ Kojima 2025, p. 5, Fig. 5.
  6. ↑ Nadeem et al. 2019, p. 4575, Table 9.
  7. ↑ Ma et al. (2011) claims 70%–95% without citation, but newer sources that are better cited, e.g. Nadeem et al. (2019), report 85%–95%.
  8. ↑ Sources vary significantly: Ma et al. (2011) indicates ~60%–70%, while newer data from Nadeem et al. (2019) reports 75%–90%.
  9. ↑ Nadeem et al. (2019) note a range of 41–75% for underground systems and 70–90% for overground systems.
  10. ↑ Includes conversion to electricity
  11. ↑ Nadeem et al. (2019) note 30–50% for low-temperature systems. The ~80% upper bound for high-temperature systems reported there likely represents thermal-to-thermal efficiency rather than full round-trip electricity conversion.
  12. ↑ Headley & Schoenung 2015, p. 3.
  13. 1 2 Kojima 2025, Abstract.

Sources