Water Usage Effectiveness (WUE) is a sustainability metric created by The Green Grid in 2011 to measure the amount of water used by datacenters to cool their IT assets.
The unit is , or, equivalently, .
The standard ISO/IEC 30134-9:2022 gives more context for accurate measure, as well as specific WUE categories and various WUE derivatives.
The WUE is a positive number. It can be 0 L/kWh (with air cooling) or up to 2.5 L/kWh (with evaporative cooling).
Facebook published a WUE of 0.22 L/kWh for their datacenter of Prineville, Oregon for the second quarter of 2012.
For the year 2025 Equinix reports a global WUE of 0.91 L/kWh for all their datacenters, and a WUE of 1.41 L/kWh for sites using evaporative cooling.
WUE is less widespread than the Power usage effectiveness (PUE), but is becoming more publicized by data center operators due to ESG considerations and/or due to water scarcity.
According to Equinix, PUE and WUE are partially opposites: with evaporative cooling the WUE increases and the PUE decreases, and with air cooling the WUE decreases (or is zero) but the PUE increases. The cooling technology of a given datacenter may be dependent on the region (and other considerations), and may be a mix of different technologies, possibly activated differently depending on the season.